8 Transponders and loop elements
50 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Use for close-and-retain systems (FSA) and all non-monitored control facilities.
The control module is installed in conventional distribution cabinets.
Programmable control pattern: static, flashing 10 s, dynamic 10/60 s
The control module SPF 5100 requires a power supply unit 24 V.
8.3.3
l facility SPF 5200
Multiple contro
The multiple control facility is used for connecting up to eight non-monitored alarm lin
the selective activation of alerting and operating devices via eight re
es or for
lay outputs (changeover
The multiple control facility occupies one address on the SIGMASYS monitored alarm line.
The m
The multiple control facility can be installed with the angle bracket in the space provided for
indicating panel.
contact).
ultiple control facility is supplied as a PCB without housing.
optional equipment in the control and
The SIGMASYS empty housing is used for remote operation.
Programmable control pattern: static, flashing 10 s
The multiple control facility SPF 5200 requires a power supply unit 24 V.
8.3.4
External alarm display module SPF 3110
The external alarm display module SPF 3110 is connected directly to t
the SIGMASYS or Sinteso detector. The line length of 10 m m
he detector output of
ust not be exceeded. The alarm
ny detector.
Dimensions (L x W x H) in mm: 82 x 82 x 46
Contr
display module support cross-loop activation from a
ol pattern: flashing 1 s
8.3.5
SIGMALOOP Splitter (V2.6)
Functionalities and Restrictions:
•
To increase the number of spur line terminals in SIGMALOOP technology with fire de-
tectors.
•
The “primary” spur line is split into up to four outgoing “secondary” spurs.
er is not assigned an address on the SIGMA spur.
r does not require external operating voltage.
•
No SIGMALOOP splitter cascading.
pur x).
OP Splitter is
without ex-
•
The SIGMALOOP splitt
•
The SIGMALOOP splitte
•
No elements are permitted on the primary spur (s
•
The cable length between the control and indicating panel and the SIGMALOOP splitter
must not exceed 10 m.
In the past, fire alarm systems were installed in a star configuration. SIGMALO
provided in firmware 2.6 and later to facilitate the replacement of these systems
tensive recabling.
Содержание SIGMASYS C
Страница 4: ......
Страница 30: ......
Страница 38: ......
Страница 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 48: ......
Страница 62: ......
Страница 84: ......
Страница 110: ......
Страница 120: ...15 Project planning examples 112 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Страница 130: ......
Страница 132: ......
Страница 134: ......
Страница 137: ......