System Manual, 06/2016, A2B00096162-AN
Connecting and commissioning
9
WARNING
Dangerous electrical voltage!
When electrical devices are used, certain parts of them have to carry dangerous voltages.
Failure to observe the operating instructions can therefore lead to serious injuries or
material damage.
Observe the operating instructions.
WARNING
Risk of injury during commissioning
•
The door movements cannot always be externally controlled while the controller is being
commissioned (in particular during the automatic determination of parameters). The light
barrier is not active during the learn run.
•
During the learn run, the force is > 70 N and the energy > 4 J.
An authorized person must therefore be posted near the door to ensure that no one else
can enter the vicinity of the door during commissioning.
Note
The motor temperature must not be below 0°C during the learn run, as otherwise the weight
of the door will be incorrectly determined, and the closing and nudge speeds may lie in
impermissible ranges.
Note
SIDOOR ATD400T RELAY - measures for complying with temperature class T3:
The following measures are required for the operation of the SIDOOR ATD400T RELAY
controller to comply with temperature class T3:
•
Use the 24 V output voltage only for operating the control inputs (max. 100 mA)
•
Use a sufficiently large (at least 350 x 350 mm), unpainted, metal mounting plate
•
The maximum drive parameters are restricted to the default values
•
The maximum air temperature of 85 °C must not be exceeded in the vicinity of the printed
circuit board