Table 4-9
Ground-Fault Detection with Cos φ/Sin φ Measurement Method Range
I
dir
Range
Status
0
Vector method is enabled
0.2 A to 30 A
Ground-fault detection with cos φ/sin φ measurement method is enabled
i
i
NOTE
In the solidly grounded system, set the I
dir
parameter to 0.
Determination of a Ground Fault with the Pulse-Location Detection
Mechanism
The
Pulse-location detection
mechanism detects a faulty feeder during a permanent ground fault in
overcompensated systems. The Pulse-location detection mechanism is applicable for resonanlt-grounded
systems only and not applicable to the undercompensated systems.
shows a simplified network with the pulse-location detection mechanism. The pulse pattern in the
ground current I
N
is generated by switching on and off a capacitor in parallel to the arc-suppression coil:
•
When the capacitor is switched on, an additional capacitive ground current is generated and the ground-
current compensation changes.
•
When the capacitor is switched off, the additional capacitive ground current no longer exists and the
ground-current compensation returns to the normal state.
4.1.21
Device Functions
4.1 Description
46
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...