Shielding / Protective Earthing
SICAM TM, Installation
91
DC6-015-2.04, Edition 10.2014
10.2. Protective Earthing / Grounding
When installing a SICAM TM system, attention is to be paid that the cabinet or rack used
features a proper protective earthing / grounding. That means, that all electrical conducting
parts must be connected large-surface and as short as possible with the cabinet spar. The
cabinet spar itself must be connected with the existing grounding system.
If these prerequisites are given, the grounding of the SICAM TM system takes place over a
connection to the mounting sheet or to the TS35 rail. (grounding wire 2,5mm
2
). A reliable
connection is achieved by using screws with contact washers.
Hint
The TS35 rail of a complete equipped pripheral element (PS+PE+8 I/O Modules) must be bolted at least
4x on metallic background. This background must be at least 40 cm wide. A mounting plate is
recommended.
Содержание SICAM TM
Страница 24: ......
Страница 60: ...Wiring Communication 60 SICAM TM Installation Edition 10 2014 DC6 015 2 04 ...
Страница 66: ...Wiring for the Reception of Time Signals 66 SICAM TM Installation Edition 10 2014 DC6 015 2 04 ...
Страница 67: ...SICAM TM Installation 67 DC6 015 2 04 Edition 10 2014 6 Wiring Watchdog and Error Content 6 1 Introduction 68 ...
Страница 74: ......
Страница 82: ...Wiring Peripheral Elements 82 SICAM TM Installation Edition 10 2014 DC6 015 2 04 ...
Страница 92: ......
Страница 118: ...Recommended and tested purchased products 118 SICAM TM Installation Ausgabedatum 10 2014 DC6 015 2 04 ...
Страница 122: ...Licensing Agreement 122 SICAM TM Installation Edition 10 2014 DC6 015 2 04 ...
Страница 124: ...Literature 124 SICAM TM Installation Edition 10 2014 DC6 015 2 04 ...