Wiring Process Peripherals
86
SICAM TM, Installation
Edition 10.2014, DC6-015-2.04
9.3.
TE-6450 – Wiring the Data Transmission
The data transmission between angle-/position sensor and TE-6450 takesplace via a
2x5x0.5mm twisted screened cable for each data interface. These cables must be conducted
interruption-free. Intermediate- or disconnection terminals are not permitted. At the TM module
side the cables are fastened and screened with screen clamp plates.
The screen clamp plates (4 pieces are supplied with the module) are fixed in the grounded
terminal points 14, 18, 24 and 28.
At the angle-/position sensor side, the cable screens must also be grounded.