67
Operation modes and settings
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
5.1.3.2.4 Setting the start/stop time
Click on the check box
Start or Stop
to make the controls for the time and date appear:
If the option
Allow arbitrary start time
is not selected, it is always necessary to enter a starting time with this time
pattern, or other times are rounded up.
Instead of the previously set start time, the
measurement can be set to start immediately,
upon the next whole minute, 10th minute, whole
hour or day.
Class A Measurement:
The standard IEC61000-4-30 requires for this class of measurement that the start is at the
stroke of a multiple of ten minutes of actual time, in order to enable comparison of data from different, spatially
separated measurements. See also the menu item
Extras
Options
Start.
Note
Even if you have set a starting time, you must click
Send + Start
to prepare measurement by
timed start.
You can specify either the
Start time
or the
Stop time
or both.
You can also use settings aid such as
arrow buttons
and
calendar
.