Open Source Software

The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the soft-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your
Siemens sales contact – against payment of the shipping and handling charges – for a period of at least 3
years after purchase of the product. We are liable for the product including the Open Source Software
contained in it pursuant to the license conditions applicable to the product. Any liability for the Open Source
Software beyond the program flow intended for the product is explicitly excluded. Furthermore any liability
for defects resulting from modifications to the Open Source Software by you or third parties is excluded. We
do not provide any technical support for the product if it has been modified.

SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual

5

E50417-H1040-C621-A2, Edition 01.2020

Содержание SICAM Q200 7KG97

Страница 1: ...Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 OPC UA PubSub MQTT Data Points V02 50 Manual E50417 H1040 C621 A2 Preface Open Source Software Table of Contents Data Points Mapping 1 Literature ...

Страница 2: ...ntract Document version E50417 H1040 C621 A2 03 Edition 01 2020 Version of the product described V02 50 Copyright Copyright Siemens 2020 All rights reserved The disclosure duplication distribution and editing of this document or utilization and communication of the content are not permitted unless authorized in writing All rights including rights created by patent grant or registration of a utilit...

Страница 3: ... 2UD1 For further information see UL database in the internet http ul com Select Online Certifications Directory and insert E228586 under UL File Number Additional Support For questions about the system contact your Siemens sales partner Customer Support Center Our Customer Support Center provides a 24 hour service Siemens AG Customer Support Center Humboldtstrasse 59 90459 Nuremberg Germany E mai...

Страница 4: ...ING WARNING means that death or severe injury may result if the measures specified are not taken Comply with all instructions in order to avoid death or severe injuries CAUTION CAUTION means that medium severe or slight injuries can occur if the specified measures are not taken Comply with all instructions in order to avoid moderate or minor injuries NOTICE NOTICE means that property damage can re...

Страница 5: ...yalty free Insofar as the applicable Open Source Software License Conditions provide for it you can order the source code of the Open Source Software from your Siemens sales contact against payment of the shipping and handling charges for a period of at least 3 years after purchase of the product We are liable for the product including the Open Source Software contained in it pursuant to the licen...

Страница 6: ...6 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 7: ...ns 13 1 4 Transient Events 14 1 5 Measured Values 15 1 6 Harmonics 18 1 7 Measured Values Min 20 1 8 Measured Values Max 23 1 9 Harmonics Max 26 1 10 Energy Values 28 1 11 Security Counters 30 Literature 31 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual 7 E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 8: ...8 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 9: ...ents 14 1 5 Measured Values 15 1 6 Harmonics 18 1 7 Measured Values Min 20 1 8 Measured Values Max 23 1 9 Harmonics Max 26 1 10 Energy Values 28 1 11 Security Counters 30 1 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual 9 E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 10: ...e SICAM Q200 7KG97xx Device Manual V02 50 General Remarks for the Mapping of Measured Values and Harmonics The described default mapping presupposes that All harmonics are enabled on the OPC UA PubSub MQTT configuration page and no imported mapping file is used By default all measured values and harmonics are transmitted as aggregated values For each aggregated measured value 3 data points average...

Страница 11: ...pIndGGIO1 ST Alm1 21 Group Indication 2 GrpIndGGIO1 ST Alm2 22 Group Indication 3 GrpIndGGIO1 ST Alm3 23 Group Indication 4 GrpIndGGIO1 ST Alm4 24 Rotation Field Clockwise IndGGIO1 ST Alm4 25 SD Card Error IndGGIO1 ST Alm5 26 Fault Record PQA_RDRE1 ST RcdMade 27 Binary Output 1 S BinOutGGIO1 ST Ind1 28 Binary Output 2 S BinOutGGIO1 ST Ind2 29 Binary Output 3 S BinOutGGIO1 ST Ind3 30 Binary Output ...

Страница 12: ...ad profile tariff 3 TOUTariffGGIO1 ST Alm31 42 Load profile tariff 4 TOUTariffGGIO1 ST Alm41 Data Points Mapping 1 2 Indications 12 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 13: ...1 forward 2 backward 3 both Table 1 2 Mapping for Voltage Variations Index MQTT Name Q200 Description Name IEC 61850 Name Remark Unit 43 Voltage Event PQA_QVVR1 ST VarStr Start Voltage variation 44 Voltage Event PQA_QVVR1 ST DipStr Start Voltage dip 45 Voltage Event PQA_QVVR1 ST SwlStr Start Voltage swell 46 Voltage Event PQA_QVVR1 ST IntrStr Start Voltage interruption 47 PQ_EVENTPHSAFF PQA_QVVR1 ...

Страница 14: ... 3 Phase AB 4 Phase C 5 Phase AC 6 Phase BC 7 Phase ABC 8 None 9 Phase ABN 10 Phase ACN 11 Phase BCN 12 Phase ABCN Table 1 3 Mapping for Transient Events Index MQTT Name Q200 Description Name IEC61850 Name Remark Unit 51 PQA_QVTR1 ST VarStr Indication 52 PQA_QVTR1 ST TrigPhs Enumeration 53 PQA_QVTR1 ST AffPhs Enumeration 54 PQA_QVTR1 ST PeakPhs Enumeration 55 PQA_QVTR1 MX MaxVTrs Measured value V ...

Страница 15: ...XU1 MX PhV net PQA0MMXU1 MX PhV net V 67 IN PQA2MMXU1 MX A neut A 68 Iavg PQA2MMXU1 MX A net PQA2MMXU1 MX A net A 69 Pa PQA2MMXN1 MX Watt PQA2MMXU1 MX W phsA W 70 Pb PQA2MMXU1 MX W phsB PQA2MMXU1 MX W phsB W 71 Pc PQA2MMXU1 MX W phsC PQA2MMXU1 MX W phsC W 72 P PQA2MMXU1 MX TotW W 73 Qa PQA2MMXN1 MX VolAmpr PQA2MMXU1 MX VAr phsA var 74 Qb PQA2MMXU1 MX VAr phsB PQA2MMXU1 MX VAr phsB var 75 Qc PQA2MM...

Страница 16: ...2MSQI1 MX ImbZroV PQA2MSQI1 MX ImbZroV 92 Zero seq comp I PQA2MSQI1 M X ImbZroA PQA2MSQI1 MX ImbZroA 93 f_10s PQA2MMXN1 MX Hz PQA2MMXU1 MX Hz Hz 94 THDR Va PQA2MHAN1 MX ThdVol PQA2MHAI1 MX ThdPhV phsA 95 THDR Vb PQA2MHAI1 MX ThdPhV phsB 96 THDR Vc PQA2MHAI1 MX ThdPhV phsC 97 THDR Vab PQA2MHAI1 MX ThdPPV phsAB PQA2MHAI1 MX ThdPPV phsAB 98 THDR Vbc PQA2MHAI1 MX ThdPPV phsBC PQA2MHAI1 MX ThdPPV phsBC...

Страница 17: ...I 3W3I 3W2I 4W1I 4W3I 104 Pst b n PQA2MFLK1 MX PhPst phsB 105 Pst c n PQA2MFLK1 MX PhPst phsC Data Points Mapping 1 5 Measured Values SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual 17 E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 18: ... 181 H_Vab 1 fundamental PQA2MHAI1 MX HPPV phsABHar 1 PQA2MHAI1 MX HPPV phsABHar 1 V 182 H_Vbc 1 fundamental PQA2MHAI1 MX HPPV phsBCHar 1 PQA2MHAI1 MX HPPV phsBCHar 1 V 183 H_Vca 1 fundamental PQA2MHAI1 MX HPPV phsCAHar 1 PQA2MHAI1 MX HPPV phsCAHar 1 V 184 to 219 H_Vab x 2 PQA2MHAI1 MX HPPV phsABHar x PQA2MHAI1 MX HPPV phsABHar x H_Vbc x2 PQA2MHAI1 MX HPPV phsBCHar x PQA2MHAI1 MX HPPV phsBCHar x H...

Страница 19: ...MHAI1 MX HA phsCHar 1 A 259 to 294 H_Ia x3 PQA2MHAN1 MX HaAmp x PQA2MHAI1 MX HA phsAHar x A H_Ib x3 PQA2MHAI1 M X HA phsBHar x PQA2MHAI1 MX HA phsBHar x A H_Ic x3 PQA2MHAI1 M X HA phsCHar x PQA2MHAI1 MX HA phsCHar x A 295 H_Pa 1 fundamental PQA2MHAN1 MX HaWatt 1 PQA2MHAI1 MX HW phsAHar 1 W 296 H_Pb 1 fundamental PQA2MHAI1 MX HW phsBHar 1 W 297 H_Pc 1 fundamental PQA2MHAI1 MX HW phsCHar 1 W 298 to ...

Страница 20: ...IN_PQA2MMXU 1 MX A phsC A 343 VN MIN_PQA2MMXU 1 MX PhV neut V 344 Vavg MIN_PQA2MMXU1 MX AvPhVPhs MIN_PQA2MMXU 1 MX AvPhVPhs V 345 IN MIN_PQA2MMXU 1 MX A neut A 346 Iavg MIN_PQA2MMX U1 MX AvAPhs MIN_PQA2MMXU 1 MX AvAPhs A 347 Pa MIN_PQA2MMXN 1 MX Watt MIN_PQA2MMXU1 MX W phsA W 348 Pb MIN_PQA2MMX U1 MX W phsB MIN_PQA2MMXU 1 MX W phsB W 349 Pc MIN_PQA2MMX U1 MX W phsC MIN_PQA2MMXU 1 MX W phsC W 350 P...

Страница 21: ...X U1 MX ActivePF phsC MIN_PQA2MMXU 1 MX ActivePF phsC 366 cos phi MIN_PQA2MMXU1 MX TotActivePF 367 Neg seq comp V MIN_PQA2MSQI1 MX ImbNgV MIN_PQA2MSQI1 MX ImbNgV 368 Neg seq comp I MIN_PQA2MSQI 1 MX ImbNgA MIN_PQA2MSQI1 MX ImbNgA 369 Zero seq comp V MIN_PQA2MSQI1 MX ImbZroV MIN_PQA2MSQI1 MX ImbzroV 370 Zero seq comp I MIN_PQA2MSQI 1 MX ImbZroA MIN_PQA2MSQI1 MX ImbZroA 371 f MIN_PQA2MMXN 1 MX Hz MI...

Страница 22: ...V phsCA MIN_PQA2MHAI1 MX ThdPPV phsCA 378 THDR Ia MIN_PQA2MHAN1 MX ThdAmp MIN_PQA2MHAI1 MX ThdA phsA 379 THDR Ib MIN_PQA2MHAI 1 MX ThdA phsB MIN_PQA2MHAI1 MX ThdA phsB 380 THDR Ic MIN_PQA2MHAI 1 MX ThdA phsC MIN_PQA2MHAI1 MX ThdA phsC Data Points Mapping 1 7 Measured Values Min 22 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H1040 C621 A2 Editio...

Страница 23: ...AX_PQA2MMXU 1 MX A phsC A 390 VN MAX_PQA2MMXU 1 MX PhV neut V 391 Vavg MAX_PQA2MMXU1 MX AvPhVPhs MAX_PQA2MMXU 1 MX AvPhVPhs V 392 IN MAX_PQA2MMXU 1 MX A neut A 393 Iavg MAX_PQA2MM XU1 MX AvAPhs MAX_PQA2MMXU 1 MX AvAPhs A 394 Pa MAX_PQA2MMXN 1 MX Watt MAX_PQA2MMXU1 MX W phsA W 395 Pb MAX_PQA2MM XU1 MX W phsB MAX_PQA2MMXU 1 MX W phsB W 396 Pc MAX_PQA2MM XU1 MX W phsC MAX_PQA2MMXU 1 MX W phsC W 397 P...

Страница 24: ... 1 MX ActivePF phsB 412 cos phi c MAX_PQA2MM XU1 MX ActivePF phsC MAX_PQA2MMXU 1 MX ActivePF phsC 413 cos phi MAX_PQA2MMXU1 MX TotActivePF 414 Neg seq comp V MAX_PQA2MSQI1 MX ImbNgV MAX_PQA2MSQI1 MX ImbNgV 415 Neg seq comp I MAX_PQA2MSQ I1 MX ImbNgA MAX_PQA2MSQI1 MX ImbNgA 416 Zero seq comp V MAX_PQA2MSQI1 MX ImbZroV MAX_PQA2MSQI1 MX ImbzroV 417 Zero seq comp I MAX_PQA2MSQ I1 MX ImbZroA MAX_PQA2MS...

Страница 25: ... phsCA MAX_PQA2MHAI1 MX ThdPPV phsCA 425 THDR Ia MAX_PQA2MHAN 1 MX ThdAmp MAX_PQA2MHAI1 MX ThdA phsA 426 THDR Ib MAX_PQA2MH AI1 MX ThdA phsB MAX_PQA2MHAI1 MX ThdA phsB 427 THDR Ic MAX_PQA2MH AI1 MX ThdA phsC MAX_PQA2MHAI1 MX ThdA phsC Data Points Mapping 1 8 Measured Values Max SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual 25 E50417 H1040 C621 A2 Editio...

Страница 26: ...MX HPhV phsCHar y 503 H_Vab 1 fundamental MAX_PQA2MHAI1 MX HPPV phsABHar 1 MAX_PQA2MHAI1 MX HPhV phsAHar 1 V 504 H_Vbc 1 fundamental MAX_PQA2MHAI1 MX HPPV phsBCHar 1 MAX_PQA2MHAI1 MX HPhV phsBHar 1 V 505 H_Vca 1 fundamental MAX_PQA2MHAI1 MX HPPV phsCAHar 1 MAX_PQA2MHAI1 MX HPhV phsCHar 1 V 506 to 541 H_Vab x5 MAX_PQA2MHAI1 MX HPPV phsABHar x MAX_PQA2MHAI1 MX HPhV phsAHar x H_Vbc x5 MAX_PQA2MHAI1 M...

Страница 27: ...PQA2MHAI1 MX HA phsAHar 1 A 579 H_Ib 1 fundamental MAX_PQA2MHA I1 MX HA phsBHar 1 MAX_PQA2MHAI1 MX HA phsBHar 1 A 580 H_Ic 1 fundamental MAX_PQA2MHA I1 MX HA phsCHar 1 MAX_PQA2MHAI1 MX HA phsCHar 1 A 581 to 616 H_Ia x5 MAX_PQA2MHAN1 MX HaAmp x MAX_PQA2MHAI1 MX HA phsAHar x A H_Ib x5 MAX_PQA2MHA I1 MX HA phsBHar x MAX_PQA2MHAI1 MX HA phsBHar x A H_Ic x5 MAX_PQA2MHA I1 MX HA phsCHar x MAX_PQA2MHAI1 ...

Страница 28: ...9 WQa_cap7 MMTN1 ST DmdVArh MMTR1 ST DmdVArh phsA MMTR1 ST DmdVArh phsA 630 WQb_cap7 MMTR1 ST DmdVArh phsB MMTR1 ST DmdVArh phsB 631 WQc_cap7 MMTR1 ST DmdVArh phsC MMTR1 ST DmdVArh phsC 632 WQ_cap MMTR1 ST DmdVArh 633 WSa7 MMTN1 ST TotVAh MMTR1 ST TotVAh phsA MMTR1 ST TotVAh phsA 634 WSb7 MMTR1 ST TotVAh phsB MMTR1 ST TotVAh phsB 635 WSc7 MMTR1 ST TotVAh phsC MMTR1 ST TotVAh phsC 636 WS MMTR1 ST T...

Страница 29: ...F_3 TOUTariffMMTN3 ST DmdWh TOUTariffMMTR3 ST DmdWh 649 WQ_IND_TARIFF_3 TOUTariffMMTN3 ST SupVArh TOUTariffMMTR3 ST SupVArh 650 WQ_CAP_TARIFF_3 TOUTariffMMTN3 ST DmdVArh TOUTariffMMTR3 ST DmdVArh 651 WS_TARIFF_3 TOUTariffMMTN3 ST TotVAh TOUTariffMMTR3 ST TotVAh 652 WP_SUP_TARIFF_4 TOUTariffMMTN4 ST SupWh TOUTariffMMTR4 ST SupWh 653 WP_DMD_TARIFF_4 TOUTariffMMTN4 ST DmdWh TOUTariffMMTR4 ST DmdWh 65...

Страница 30: ...e Web UI of the device Table 1 10 Mapping for Security Counters Index MQTT Name Q200 Description Name IEC61850 Name Remark 657 GSAL1 ST AuthFail The counters start with 0 when the device is restarted or reset 658 GSAL1 ST Login 659 GSAL1 ST Logout 1 11 Data Points Mapping 1 11 Security Counters 30 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H10...

Страница 31: ...iterature 1 SICAM Q200 7KG97xx Device Manual V02 50 E50417 H1040 C606 A7 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual 31 E50417 H1040 C621 A2 Edition 01 2020 ...

Страница 32: ...32 SICAM Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97 Manual E50417 H1040 C621 A2 Edition 01 2020 ...