Measured Values (Max.)
Table 1-7
Mapping for Measured Values (Max.)
Index
MQTT
Name Q200
(Max. Value of)
Name IEC61850 and OPC UA PubSub
Unit
1P
3W1I
3W3I
3W2I
4W1I
4W3I
381
Va
MAX_PQA2MMXN
1$MX$Vol
–
–
–
MAX_PQA2MMXU1$MX
$PhV$phsA
V
382
Vb
–
–
–
–
–
MAX_PQA2MMXU
1$MX$PhV$phsB
V
383
Vc
–
–
–
–
MAX_PQA2MMXU
1$MX$PhV$phsC
V
384
Vab
–
MAX_PQA2MXU1$MX
$PPV$phsAB
–
MAX_PQA2MXU1
$MX$PPV$phsAB
V
385
Vbc
–
MAX_PQA2MMXU1$MX
$PPV$phsBC
–
MAX_PQA2MMXU
1$MX$PPV$phsBC
V
386
Vca
–
MAX_PQA2MMXU1$MX
$PPV$phsCA
–
MAX_PQA2MMXU
1$MX$PPV$phsCA
V
387
Ia
MAX_PQA2MMXN
1$MX$Amp
MAX_PQA2MMXU1$MX$A$phsA
A
388
Ib
–
–
MAX_PQA2MM
XU1$MX$A
$phsB
–
MAX_PQA2MMXU
1$MX$A$phsB
A
389
Ic
–
–
MAX_PQA2MM
XU1$MX$A
$phsC
–
MAX_PQA2MMXU
1$MX$A$phsC
A
390
VN
–
–
–
–
–
MAX_PQA2MMXU
1$MX$PhV$neut
V
391
Vavg
–
MAX_PQA2MMXU1$MX
$AvPhVPhs
–
MAX_PQA2MMXU
1$MX$AvPhVPhs
V
392
IN
–
–
–
–
–
MAX_PQA2MMXU
1$MX$A$neut
A
393
Iavg
–
–
MAX_PQA2MM
XU1$MX
$AvAPhs
–
MAX_PQA2MMXU
1$MX$AvAPhs
A
394
Pa
MAX_PQA2MMXN
1$MX$Watt
MAX_PQA2MMXU1$MX$W$phsA
W
395
Pb
–
–
MAX_PQA2MM
XU1$MX$W
$phsB
–
MAX_PQA2MMXU
1$MX$W$phsB
W
396
Pc
–
–
MAX_PQA2MM
XU1$MX$W
$phsC
–
MAX_PQA2MMXU
1$MX$W$phsC
W
397
P
–
MAX_PQA2MMXU1$MX$TotW
W
398
Qa
MAX_PQA2MMXN
1$MX$VolAmpr
MAX_PQA2MMXU1$MX$VAr$phsA
var
399
Qb
–
–
MAX_PQA2MM
XU1$MX$VAr
$phsB
–
MAX_PQA2MMXU
1$MX$VAr$phsB
var
400
Qc
–
–
MAX_PQA2MM
XU1$MX$VAr
$phsC
–
MAX_PQA2MMXU
1$MX$VAr$phsC
var
401
Q
–
MAX_PQA2MMXU1$MX$TotVAr
var
1.8
Data-Points Mapping
1.8 Measured Values (Max.)
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
23
E50417-H1040-C621-A2, Edition 01.2020