6 Getting Started
6.4 System Requirements
96
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Connect the cables of the supply voltage on the terminal side of the device at
terminal block H
as follows:
Supply from the Alternating Voltage System
Terminal N/-:
Neutral conductor of the supply voltage
Terminal L/+:
Phase of the supply voltage
Terminal
:
Protective grounding terminal
Supply from a Direct Voltage Source
Terminal N/-:
Negative supply voltage
Terminal L/+:
Positive supply voltage
Terminal :
Protective
grounding
terminal
Terminals
Terminals for supply voltage (H), inputs for current measurement (E), inputs for voltage measurement (F), bi-
nary inputs (U) and binary outputs (G) on the terminal side:
Conductor cross-section, rigid max.
2.5 mm² (AWG 14)
Conductor cross-section (conductor with ferrule)
1.5 mm² (AWG 16)
Conductor cross-section (conductor with ferrule, terminal F)
2.5 mm² (AWG 14)
Tightening torque
0.4 Nm to 0.5 Nm (3.5 in-lb to 4.5 in-lb)
RS485 interface (J) on the terminal side:
RS485 cable with 9-pole D-sub socket
Ethernet interface (Z) on the top side:
Ethernet patch cable or crossover cable
Voltage measuring inputs:
In the case of a
direct connection
and
transformer connection
, the device has
to be safeguarded with a
listed 10 A backup fuse
or a listed 10 A miniature circuit breaker. When using voltage
transformers, their secondary connections must never be short-circuited!
6.4
System Requirements
To operate SICAM Q100 with a PC or notebook, the following system requirements must be met:
•
PC or notebook with Intel Pentium processor (or compatible type); clock frequency min. 800 MHz
•
Operating system: Microsoft Windows XP Professional and Windows 7 with Internet Explorer 6.0 (or
higher)
•
Minimum 1 GB RAM primary storage
•
VGA display 1024 x 768 with truecolor
NOTE
Always connect the grounding at the SICAM Q100 to the terminal for the protective conductor
(terminal block H).
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...