5 Energy Management
5.1 Load-Profile Determination
81
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
5.1.2
Methods of Load-Profile Determination
SICAM Q100 supports the following load-profile determination methods:
•
Fixed Block
•
Rolling Block
Fixed Block method
The
Fixed Block method
with a measuring-period length of 15 minutes is the default setting. In addition, the
number of subperiods
of this method is set to
1
. The load-profile data are determined at the end of every
measuring period and stored in the ring buffer and transmitted, if necessary, or displayed on the user interface.
Figure 5-2
Determination of the load profile according to the Fixed Block method
NOTE
The parameterization of the load profile is described in detail in chapter 8.3.5.1. Note the information specified
there.
Measuring
period
15
t [min]
45
30
0
1
3
2
Duration of a
measuring period
Time of the recording of
the load profile data of the
ended measuring period
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...