13 Technical Data
13.1 General Device Data
320
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
13.1
General Device Data
13.1.1
Power Supply
Direct Voltage
Alternating Voltage
Rated input voltages
24 V to 250 V
Admissible input voltage tolerance
±20 %
Permitted ripple of the input voltage
15 %
Maximum inrush current
At
110 V
< 15 A
At 220 V to 300 V
22 A; after 250 µs: < 5 A
Maximum power consumption
6 W
Rated input voltages
110 V to 230 V
System frequency at AC
50 Hz/60 Hz
Admissible input voltage tolerance
±20 %
Permitted harmonics
2 kHz
Maximum inrush current
At
115 V
< 15 A
At 230 V
22 A; after 250 µs: < 5 A
Maximum power consumption
16 VA