
8 Operation at Use of a PC
8.3 Configuration of the Device
213
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
The factory settings of the
Source of output x
parameters are controllable indications, for example,
Indication 3 from Remote,
and can be controlled via the Modbus TCP or IEC 61850 protocols. You can also
parameterize an internal indication from SICAM Q100 in the list boxes.
If one or two
SICAM I/O Units
have been selected as subdevices, the indications on the status of the binary
inputs of these devices are also available in the group indications (see chapter 8.3.3.2.2), the indications of the
LEDs (see chapter 8.3.3.1.4), and the indications of the binary outputs (chapter 8.3.3.1.3).
8.3.7.5.2
Parameter Settings of the SICAM I/O Unit 7XV5673 (Subdevice)
Settings of the Ethernet Communication of the SICAM I/O Unit
NOTE
A detailed description of all parameter settings of the SICAM I/O Unit 7XV5673 and a description of that device
is given in the Device Manual, order number E50417-H1040-C484.
Table 8-31
Settings of the Ethernet Communication in the SICAM I/O Unit Subdevice
Parameter
Default Setting
Setting Range
IP address
At
IP address
, enter the same IP address as in
SICAM Q100
I/O Unit sub-
device
under
Server IP address
.
SICAM Q100 and SICAM I/O Unit must have different IP addresses.
Subnet mask
255.255.255.0
Identical to the subnet mask of the SICAM Q100
Default gateway
192.168.0.1
Any
Ethernet switch on
no
Activation of the second port of the internal Ether-
net switch
Bus protocol/Operating
mode
I/O Mirror server
You must select
I/O Mirror Server
for connection to
the SICAM Q100.
Operating Mode I/O Mirror Server
Port number
51 000
Port number for the Ethernet communication
between SICAM Q100 and SICAM I/O Unit
Communication super-
vision time
8 (*10 ms)
–
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...