
9 Operation at Use of a PC
9.3 Configuration of the Device
207
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.6 Report Configuration
The
Report configuration
allows you to parameterize the PQ threshold parameters (
User defined
). You can
adjust the process connections to the installation environment and enter different operational settings.
Alternatively, you can use the default values according to
EN 50160 LV&MV
or
EN 50160 HV
.
Default Settings and Setting Ranges
Table 9-20 Report Configuration
Parameter
Default Setting
Setting Range
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
-
Any text displayed in the
printout of the power quality
report
Power Quality Report
Evaluation mode according to:
EN 50160 LV&MV
EN 50160 LV&MV
EN 50160 HV
User defined
Flagging acc. to
IEC 61000-4-30
no
no
yes
Power frequency
99.5 % of measurement should be in -1.0 % to 1.0 % deviation of the
power frequency.
100 % of measurement should be in -6.0 % to 4.0 % deviation of the
power frequency.
Any setting for user-defined
evaluation mode
Power supply voltage magnitude
95 % of measurement should be in -10.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
100 % of measurement should be in -15.0 % to 10.0 % deviation of
the nominal/declared supply voltage.
Any setting for user-defined
evaluation mode
Flicker severity
95 % of measurement should be less than 1.0
Voltage unbalance
1)
95 % of measurement should be less than 2.0 %.
100 % of measurement should be less than 3.0 %.
Any setting for user-defined
evaluation mode
Subgroup Total Harmonic Distortion factor (THDS)
95 % of measurement should be less than 8.0 %.
Any setting in % for user-
defined evaluation mode
MAN_SICAM_Q100_US.book Page 207 Wednesday, June 5, 2019 9:31 AM