
9 Operation at Use of a PC
9.3 Configuration of the Device
184
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.5
Energy Management
9.3.5.1 Load Profile
Default Settings and Setting Ranges
1)
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical.
Number = 2 to 5: Rolling Block method
Length of the subperiod: The length of the subperiod is an integer part of a full hour.
Length of measuring period: The length of the measuring period cannot be configured directly. It is defined
as the product of the length of the subperiod and the number of subperiods:
Length of measuring period = n x length of subperiod; n = number of subperiods
2)
Under 3-wire Network (Delta), the selection of Q1 should not be used.
Parameterizing the Load Profile
To change the
Load profile
settings, proceed as follows:
Table 9-10
Load Profile
Parameter
Default Setting
Setting Range
Subperiode time
15 minutes
1 min to 6 min in 1-min steps, 10 min, 12 min,
15 min, 20 min, 30 min, 60 min
Number of subperiods
1)
1
1 to 5
Synchronization source
Internal clock
None
Protocol
Binary input 1
Binary input 2
Internal clock
Kind of used reactive power
Q1
Q1
2)
Qn
Qtot
MAN_SICAM_Q100_US.book Page 184 Wednesday, June 5, 2019 9:31 AM