Communication
6.2.4 Information mapping table
SICAM P30 P31 P32, 3-phase Current Power Meter, User Manual
E50417-H8940-C561-
4
, Release Date
06.2018
34
6.2.4
Information mapping table
Common Parameters
Alarm Parameters
Parameter Address
Data
Type
Length
R/W
Data
Range
Remark
Modbus address
0000 H
unsigned int
2 bytes
R/W
0...247
Baud rate of
communication
0001 H
unsigned int
2 bytes
R/W
0...6
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
5: 600 bps
6: 1200 bps
16 UBs of current
conversion ratio
0004 H
unsigned long
4 bytes
R/W
0...99999999
CT ratio=set val-
ue/10,000, 10,000
as default when
CT=0
16 LBs of current
conversion ratio
0005 H
Clearing extreme
value
0006 H
unsigned int
2 bytes
W
Arbitrary value
Parity bit
0020 H
unsigned int
2 bytes
R/W
0...3
0: 8E1
1: 8o1
2: 8n1
3: 8n2
Parameter Address
Data
Type
Length
R/W
Data
Range
Remark
Relay output 1
0100 H
unsigned int
2 bytes
R/W
0...1
Write operation is valid
when "alarm control
byte" is 0 or 2
Relay output 2
0101 H
unsigned int
2 bytes
R/W
0...1
Write operation is valid
when "alarm control
byte" is 0 or 1
Binary inputs
0102 H
unsigned int
2 bytes
R
High byte: Binary input
status (note)
Low byte: Relay output
status
Alarm control
byte
0103 H
unsigned int
2 bytes
R/W
0...3
0: turn off alarm function
1: relay output 1 is used
for alarm
2: relay output 2 is used
for alarm
3: relay output 1 and 2
are all used for alarm