
5
5.7 Input / Output Modules
97
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
2. Parameterize the I/O modules.
3. Send the new configuration to the device, as soon as the connection to the device has been
established.
5.7.4
Analog Outputs (optional)
The analog outputs (optional) allow you to output internal measurement values as analog values
in the range of 0 mA to 20 mA. This feature represents a measuring transducer.
Proceed as follows:
1. Please select
Slot A
to configure analog outputs.
2. Activate/Deactivate one or both analog outputs by ticking the corresponding check box under
1.
and/or
2.
3. For each analog output used, choose the
Measured value
together with the
Test point
and
set the signal range in the fields
from
and
to
.
4. Select the current range of the I/O module:
0..20 mA
or
4..20 mA
.
Note
The output of analog values can be controlled via Modbus, IEC 60870-5-103 or Profibus proto-
col. Select the output mode first in screen
further setting
(see chapter 4.4.8) in
AO settings
and choose
holding
or
default
mode in screen
Analog output settings
.
Deactivate the channel which will be controlled by communication protocol in dialog
Analog out-
puts
.