5
5.8 Additionals
104
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5.8.3
Limit Value Groups
In SICAM P, you can parameterize up to 7 limit value groups. For limit value group 7, only volt-
ages are allowed.
Every
limit value group
provides the option to monitor whether the
measurements
exceed (
>
)
or fall short of (
<
) a measured value that is entered. In each of the seven limit value groups, up
to six measured quantities (no power quantities) can be
ANDed
or
ORed
.
The limit value groups set can be allocated either to binary outputs or to the internal counters.
The oscilloscope can be triggered using a limit value group 1 to 6.
•
Filter time: Time for which a threshold breach must remain in order to trigger an alarm. Input
from 0.0 s to 9.9 s.
•
Hysteresis: Entry from 0.1 % to max. 10 %. The value relates to the nominal values for the
individual measured values.
Note
To make sure that limit violations will be registered, enter a filter time
≥
1 s.
Note
If the device provides additional analog inputs (optional), you can use external measurement sig-
nals for limit-value monitoring.
Note
Limit value group 7 allows you to monitor the measured voltages in real time and logs the mea-
sured value that caused a limit violation.