Power direction
This parameter allows you to set the operating mode of the SICAM P:
•
Load
(industry mode, standard)
this means:Power positive = Energy demand
Power negative = Energy supply
•
Generator
(Power generation mode)
this means:Power negative = Energy demand
Power positive = Energy supply
Counter assignment
Internal
counters 1 to 4
can be displayed in the digital measured value screens of the SICAM P.
You can assign the four internal counters to the max. 6
limit values groups
here.
Zero point suppression
The zero suppression enables the definition of the
measuring range start
in % of the measuring
range end. Can be selected from 0.0 % to 10.0 % of the upper limit of the measurement range
(default setting: 1.000 %).
5.8.2
Device Code
Setting the device code secures the SICAM P against unauthorized changes.
When the code is activated, you are prompted to enter the password when you call up the
Note
Due to its high precision, SICAM P can measure voltages and currents even without measuring
values connected to the device. If you do not want this behaviour in your application, you can
suppress measuring below a certain threshold.