5 Getting Started
5.2 Assembly
44
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
5.2
Assembly
5.2.1
General Assembly Notes
SICAM MMU is intended to be installed on a DIN rail, e.g. in a control cabinet.
•
The installation site must be vibration-proof. The permitted ambient temperature must be observed (see
the technical data in chapter 13).
•
Operating the device outside the permitted operating temperature range can lead to measuring errors and
device failure.
•
The terminals are designed for wire cross-sections of 2.5 mm² max.
•
The device must not be exposed to condensation during operation.
•
The device must be installed in a location where it is not exposed to direct sunlight and strong temperature
variations.
WARNING
Do not touch any live parts.
Non-observance may lead to death or serious injury.
✧
After installation of the device and wiring, close the control cabinet.