9 Communication
9.3 IEC 60870-5-104
197
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.3.7
IEC 60870-5-104 Diagnosis
The diagnosis for IEC 60870-5-104, see chapter 7.5.5.2, allows the parameters and communication to be
analyzed and the diagnosis counters to be reset.
Fig. 9-7
IEC 60870-5-104 Diagnosis
All diagnosis counters are signless 32-bit values (counting maximum: 4 294 967 295).
The diagnosis counters are set to 0 under the following conditions:
•
Device restart
•
Clicking
Clear counters
in the input/output window
•
Activation of communication via IEC 60870-5-104 during parameterization
Diagnosis Parameters
•
Redundancy mode:
Set redundancy method:
- none-
- IEC 60870-5-104
- Equal connections
•
Connection overflows:
Counter of attempts to set up more connections than permitted:
- More than 1 connection for redundancy method
-none-
- More than 2 connections for redundancy methods
IEC 60870-5-104
and
Equal connections
•
Port number:
Set TCP port number for the connections
SICAM-MMU_7KG9663_US.book Page 197 Monday, December 7, 2015 12:22 PM