7 Operation
7.5 Maintenance
132
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
✧
Click
Browse...
The
Choose File to Upload
dialog opens.
Fig. 7-49
Choose File to Upload Dialog
✧
Select the desired update (extension .pck) in the directory.
✧
Click
Open
.
The selected path is inserted in the input/output window, figure 7-48, into the
Browse...
field.
✧
Click
Open
.
✧
After approx. 2 s, the message
Action was successful!
is displayed in the input/output window.
Device firmware, default set of parameters, text libraries, HTML files or parts thereof are uploaded within
one minute.
The device then restarts automatically.
7.5.2
Calibration
The chapter 10 gives a detailed description of the calibration of the measuring ranges of alternating voltage,
alternating current, and voltage in the neutral conductor (V
N
). It explains the
•
measurement setup and the
•
calibration procedure.
NOTE
Do not switch off the supply voltage during the upload process as this can lead to data loss.
SICAM-MMU_7KG9663_US.book Page 132 Monday, December 7, 2015 12:22 PM