7 Operation
7.3 Configuration of the Device
105
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the changes
and then enable the device configuration as described in
Activating the Set of Parameters
7.3.3.2.2
Group Indications
In the
Select automation functions
menu, up to 4
Group indications
can be parameterized and each of them
can be assigned up to 4 logically linked single-point indications. The single-point indications can be inverted.
Default Settings and Setting of the Group Indications
NOTE
Select
Measurand
-none-
to disable the respective limit violation indication.
NOTE
Which quantities are offered in the
Measurand
list box depends on the configured network type. The
Network
type
is specified in the
Process connections
submenu,
AC measurement
input/output window, see
Table 7-6
Group Indications
Parameter
Default Setting
Setting Range
Source
-none-
Acc. to list box
Source inverted
no
no
yes
Logic operation
NONE
AND
OR
NONE (no logic operation selected)
Group indication name
Group Indication x
(x = 1 to 4)
Any