Service
SICAM RTUs, User Manual SICAM CMIC
289
DC8-001-2.09, Edition 08.2016
6.2
Checks and System Display
The single system elements carry out checks of the hardware and software. If an error is de-
tected, this leads
•
to a signaling on the LED display
•
dependent of the severeness of the error possibly
─
to an abort of the startup
─
in operation to a shutdown of the modules or firmware
After an errorless startup of a system element further checks are carried out.
6.2.1
Checks
during
Startup
Startup (step)
RY
ER
Error/reaction
Power-up or reset
™
˜
Start startup
™
•
Module defective
•
Massive error in the program memory
Check of the code memory (flash
PROM)
™
˜
PROM error (code)
•
Module is shut down
•
Startup is aborted
Check of the data memory (RAM) with
address error check
™
˜
RAM error (data)
•
Module is shut down
•
Startup is aborted
Check whether SD card is present
™
˜
SD card not present
Check of the checksum of all parame-
ter files and firmware files on the SD
card
™
˜
Checksum error on the SD card
•
Diagnosis information is set
Check whether all parameters on the
SD card are present
™
˜
Parameter files incomplete
•
Firmware is shut down
•
Startup is aborted
Check whether all firmware files on the
SD card are present
™
˜
Firmware code incomplete
Check whether the firmware code of
the subordinate system elements (pro-
tocol elements, peripheral element) is
current
™
˜
If not,
at a later time
Revision check of the parameters in
the parameter memory
™
˜
If the parameters are not current, they are
loaded from the SD card
Check parameter memory (flash-
PROM)
™
˜
Checksum error of the parameters
•
Firmware is shut down
•
startup is aborted
Initiate the startup of the subordinate
system elements
™
˜
Check for accordance of the parame-
terized HW configuration with the me-
chanical configuration (I/O modules)
™
˜
Configuration error
•
the wrongly configured or defective module
is not operational
•
successional modules are not operational
Check of the configuration for pulse
command output
™
˜
Configuration error
•
Pulse command output is locked for all
modules
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...