Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
247
DC8-001-2.09, Edition 08.2016
5.2.1.6 Command Processing According to IEC 60870-5-101/104
If a command (Activation,
ACT
) is generated by the controller and output on a peripheral ele-
ment, then the messages for command acknowledgement (
ACTCON
) and command termina-
tion (
ACTTERM
) are generated with the corresponding output address of the control.
If the output address of the control is the same as the input address, then both messages are
automatically transmitted again to the control.
If an
ACT
remains in the control (target = control, no periphery), then an
ACTCON
,
ACTTERM
that is to be possibly simulated can be generated in 1 cycle pass. For this the cause of trans-
mission for the command must be set to
0
and the spontaneous bit to
1
. Then one
ACTCON
and one
ACTTERM
respectively will be transmitted.
Example:
LD 0
ST 0_045_001_001_001.COT
LD 1
ST 0_045_001_001_001.S
If this function is not used, the
ACTCON
and
ACTTERM
can also be generated individually (for
this at least 2 cycle passes are required).
Note
The corresponding typ identification can be generated by means of Verwendung of utilization of the com-
mand "with/without time" (for instance TI 45/TI 58).
Single Command and Double Command
Single commands (TI 45) can be generated by the IL only with the states
0
(OFF) only with
COT
=
7
,
10
(
CON
,
TERM
) and
S
=
1
1
(ON)
Double commands (TI 46) can be generated by the IL only with the states
01
(OFF)
10
(ON)
Other states will not generate a command output.
You find the details for the processing of commands in the manual
SICAM RTUs Common
Functions System and Basic System Elements, chapter "Automation", section "Treatment for
Commands to the Open-/Closed-Loop Control Function according to IEC 60870-5-101/104"
.
5.2.1.7 Generation of Integrated Totals
There are two possibilities of integrated total generation in the control:
•
Spontaneous transmission with change
Automatically if the input address is
unequal
to the output address of the controller.
•
Behavior according to parameter setting of the digital inputs (remote control)
Automatically if the input address is
equal
to the output address of the controller.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...