Preparing the Engineering
SICAM RTUs, User Manual SICAM CMIC
101
DC8-001-2.09, Edition 08.2016
3.8.2.9 Exceptions with Engineering via SICAM WEB
The parameter records in the SICAM TOOLBOX II and in the SICAM WEB are basically iden-
tical structured. However, for the engineering via SICAM WEB some simplifications exist,
hence the following functions are not supported or implemented in another manner:
•
HW configuration basic system element (BSE)
The BSE is automatically configured as soon as a SD card with the firmware
CPC80
has
been installed.
•
System technique peripheral element (PE)
After the configuration of the PE the I/O modules must be configured in the OPM II. With
the engineering via SICAM WEB the I/O modules are configured automatically.
•
Process technique peripheral element (PE)
In contrast to the OPM II no images are applied, for each I/O module an assignment page
and a parameter page exist.
In the assignment page the usage of the I/Os is defined (according to the assignment in
the SICAM TOOLBOX II).
In the setting page the previously configured I/Os are parameterized. There appear only
the parameters relevant for the defined usage.
•
Process technique protocol element (PRE)
In contrast to the OPM II no images are applied, the process technique is provided as
spreadsheets (send detailed routing, receive detailed routing).
•
Loading firmware of protocol elements
Protocol elements can not be loaded slot-selectively. If for instance on PRE0 and on PRE1
the system element
UMPST0
is configured, both are loaded.
•
Message simulation
The message simulation is not supported (inserting of arbitrary messages into the system).
However, there is the possibility of displaying current process values of the periphery (bi-
nary information states, integrated totals, measured values) and to set process values
(commands, setpoint commands).
•
Data flow test
The data flow test is not supported (different log points, filters, etc.).
•
Revision interrogation
The current firmware revision of the basic system element is displayed in the header of the
user interface, the revisions of the additional system elements (PRE, PE) in the drop-down
menu on the configuration page.
•
Application program
A graphical function diagram (FUD) creation is not possible, only an instruction list (IL) with
ASCII format can be loaded into the target device.
•
Test of the application program
Offline simulation of the application program is not possible. A simplified online test (state
display, forcing of a selectable signal) is available.
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...