Data traffic
6.2 Cyclic data traffic
PROFINET Proxy SPP2000
36
Equipment Manual, 03/2022, L1V30814715D-01
6.2.4
Basic type 3
Structure
The structure of basic type 3 is fixed. Basic type 3 is 116 bytes long.
Basic type 3 contains the control bytes.
Note
Basic type 3 is only available for PAC3200T.
Table 6- 3
Basic type 3 transfers the following input data:
Byte
Data value
Format
Unit
0 ... 3
Status information
Unsigned long
—
4 ... 7
Voltage L1-N
Float
V
8 ... 11
Voltage
L2-N
Float
V
12 ... 15
Voltage L3-N
Float
V
16 ... 19
Voltage L1-L2
Float
V
20 ... 23
Voltage L2-L3
Float
V
24 ... 27
Voltage L3-L1
Float
V
28 ... 31
Current L1
Float
A
32 ... 35
Current L2
Float
A
36 ... 39
Current L3
Float
A
40 ... 43
Power factor L1
Float
—
44 ... 47
Power factor L2
Float
—
48 ... 51
Power factor L3
Float
—
52 ... 55
THD voltage L1
Float
%
56 ... 59
THD voltage L2
Float
%
60 ... 63
THD voltage L3
Float
%
64 ... 67
THD current L1
Float
%
68 ... 71
THD current L2
Float
%
72 ... 75
THD current L3
Float
%
76 ... 79
Line frequency
Float
Hz
80 ... 83
3-phase average current
Float
A
84 ... 87
Total apparent power
Float
VA
88 ... 91
Total active power
Float
W
92 ... 95
Total reactive power (VARn)
Float
Var
96 ... 99
Total power factor
Float
—
100 ... 103
Amplitude unbalance voltage
Float
%
104 ... 107
Amplitude unbalance current
Float
%
108 ... 111
Length of last period
Unsigned long
s
112 ... 115
Neutral current
Float
A
Содержание SENTRON PROFINET Proxy SPP2000
Страница 1: ......
Страница 2: ......
Страница 12: ......
Страница 34: ......
Страница 81: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 79 Dimensional drawings 10 ...
Страница 82: ......
Страница 89: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 87 ...
Страница 90: ......