14 Operating Parameters
14.4 Recording and Reporting
255
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.4.4
Memory Management
1)
The memory sizes for event list, PQ records and fault records can be changed.
2)
The memory size for continuous recording is calculated automatically and forms the difference to 100 %
of the total memory size. The maximum total memory size of 100 % cannot be exceeded due to
parameterization errors.
3)
If the residual storage capacity falls below 30 %, then the activation is not possible. In this case appear
the report was not successfully action in the status line.
Parameter
Default Setting
Setting Range
Splitting
Event recorder
1.0 %
1 % to 33 %
1)
Measurement recorder
35.0 %
(the recording time depends on
the aggregation interval)
33 % to 65 %
1)
Trend recorder
61.0 %
(residual storage capacity)
31 % to 63 %
2) 3)
Fault recorder
3.0 %
(Numbers of records depends on
the fault record time.)
3 % to 35 %
1)