7 Operation at Use of a PC
7.3 Configuration of the Device
136
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.2 Trigger Management
Default Settings and Setting Ranges
Table 7-11
Trigger Management
Parameter
Default Setting
Setting Range
Voltage trigger limits
Trigger active
no
no
yes
Tolerance unit
Percentage
Percentage
Numerical
Lower threshold
90.00 %
of the primary nominal
voltage
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Upper threshold
110.00 %
of the primary nominal
voltage
100.0 % to 10 000.0 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Hysteresis
2.00 %
of the primary nominal
voltage
0.0 % to 50.0 % of the of the primary
nominal voltage
Current trigger limits
Trigger active
no
no
yes
Tolerance unit
Percentage
Percentage
Numerical
Lower threshold
90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold
110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
Hysteresis
2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Waveform capture setting
Total recording duration
2.0 s
0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio
10 %
0 % to 30 % in 5-% steps
Record ph-ph voltage
no
no
yes
Содержание SENTRON PAC5100
Страница 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 242: ...13 Operational Indications 242 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...