7 Operation at Use of a PC
7.3 Configuration of the Device
134
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5
Recording and Reporting
7.3.5.1 Event Recorders
Default Settings and Setting Ranges
Table 7-10
Event Recorders
Parameter
Default Setting
Setting Range
Supply voltage
Swell threshold
110 %
105 % to 140 % in 5-% steps
Dip threshold
90 %
75 % to 95 % in 5-% steps
Interruption threshold
5 %
1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis
2 %
1 % to 6 % in 1-% steps
Frequency
Underfrequency threshold
1 %
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Overfrequency threshold
1 %
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
Voltage unbalance threshold
5 %
1 % to 5 % in 1-% steps