7 Operation at Use of a PC
7.3 Configuration of the Device
125
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.3.2 Automation Functions
7.3.3.2.1
Limit Settings
In the
Select automation functions
menu you can set upper or lower limits for up to 16 measured values.
Limit violations of the upper or lower value range can be output as indications. Up to 4 limiting value violations
can be signaled at the device via the two binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit
violations can be sent to peripheral devices via Ethernet.
The programmable limits are divided into two groups
Limits 1-8
and
Limits 9-16
. The parameterization is
identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 7-6
Limit Settings
Parameter
Default Setting
Setting Range
Measurand
-none-
Acc. to list box
(see Operating Parameters)
Limit
0.0
-1 000 000 000 to 1 000 000 000 (unit)
Limit type
Lower
Lower
Upper
Hysteresis (%)
1.0
0.0 to 10.0
Violation indication
Limit Violation x
(x = 1 to 16)
The name of the limit violation indication is
customizable.
Содержание SENTRON PAC5100
Страница 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 242: ...13 Operational Indications 242 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...