Description
3.4 Load profile
SENTRON PAC4200
30
Manual, 09/2008, A5E02316180B-01
Configuring load profile recording
You can adapt load profile recording using the configuration software or on the display of the
device. The following parameters influence the recording:
●
Length of the demand period or subperiod
●
Number of subperiods per demand period. This number defines the method for recording
the load profile ("fixed block" or "rolling block")
●
Type of synchronization
You can also set the following parameter with the configuration software:
●
Type of reactive power VAR
tot
, VAR
1
, or VAR
n
You can find more information about parameterization on the device display in the chapter
"Parameterizing", "Power demand".
Changing the configuration during operation: If the period length or the number of subperiods
is changed, this directly influences the load profile recording. The device stops the current
recording and clears all data in the load profile memory. Changing the configuration has no
effect on the device counter. The device is not reset.
Load profile recording methods
SENTRON PAC4200 supports the following load profile recording methods:
●
Fixed block
●
Rolling block
The default setting is the fixed block method with a demand period length of 15 minutes.
Fixed block method
The load profile data is calculated and stored at the end of each demand period.
'HPDQG
SHULRG
'HPDQGSHULRG
'HPDQGSHULRG
'HPDQGSHULRG
(QGRI
GHPDQGSHULRG
W>PLQ@
Figure 3-3
Load profile, fixed block method
Содержание SENTRON PAC4200
Страница 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Страница 84: ...Connecting 6 5 Grounding of the Ethernet cable SENTRON PAC4200 84 Manual 09 2008 A5E02316180B 01 ...
Страница 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Страница 146: ...Parameterizing 9 2 Parameterizing the operator interface SENTRON PAC4200 146 Manual 09 2008 A5E02316180B 01 ...
Страница 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Страница 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Страница 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...