Startup
7.5 BASIC PARAMETERS
SENTRON PAC3200
98
Manual, 02/2008, A5E01168664B-04
Example:
You want to measure using voltage transformers for 10000 V/100 V on a 10 kV system.
For this purpose, enter:
1.
USE PTs?: On:
2.
PT PRIMARY: 10000V
3.
PT SECONDARY: 100V
Figure 7-7
"VOLTAGE INPUTS" device setting
7.5.1.4
Setting the voltage input
The factory setting for the measuring reference voltage is 400 V. At initial startup, the
following steps must be carried out if the available measuring voltage deviates from this.
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
3.
Go to the "VOLTAGE INPUTS" device setting:
<F2>
or <F3>
Figure 7-8
"VOLTAGE INPUTS" device setting
4.
Open edit mode of the "VOLTAGE INPUTS" device setting:
<F4>
5.
Set the desired value:
<F2>
and <F3>
6.
Accept the value:
<F4>
The value of the voltage input is permanently saved and becomes effective immediately.
The display returns to display mode.
7.
Return to one of the selection menus or to the measured values display:
<F1>
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...