Startup
7.5 BASIC PARAMETERS
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
97
7.5.1.3
Setting the conversion ratio of the voltage transformer
The factory setting is measurement direct on the system. At initial startup, the following steps
must be carried out if you want to measure using voltage transformers.
The conversion ratio can only be set if measurement using voltage transformers is set in the
device settings. Only then are the fields for primary and secondary voltage visible on the
display.
Figure 7-6
Device setting "USE PTs?"
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the current settings.
If the "PT PRIMARY" and "PT SECONDARY" fields are not visible, direct measurement
on the system is set. Switch from direct measurement to measurement using voltage
transformers. You can find the instructions for this in the "Measurement using voltage
transformers" chapter.
3.
Go to the "PT PRIMARY" device setting:
<F2>
or <F3>
4.
Open edit mode of the "PT PRIMARY" device setting:
<F4>
5.
Set the desired value:
<F2>
or <F3>
6.
Accept the value:
<F4>
The value of the primary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
7.
Go to the "PT SECONDARY" device setting:
<F2>
or <F3>
Proceed in exactly the same way as when entering the primary voltage.
The value of the secondary voltage is permanently saved and becomes effective
immediately.
The display returns to display mode.
8.
Return to one of the selection menus or to the measured values display:
<F1>
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...