Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
139
PULSE LENGTH The field is available with the action "ENERGY PULSE".
Pulse length.
Range: 30 to 500 ms
Default: 100 ms
The minimum length of the pulse pause corresponds to the pulse
duration specified.
DIGITAL INPUT
Figure 9-11 "DIGITAL INPUT" device setting
ACTION
Method of using the digital input:
NONE:
The digital input is switched off.
PULSE INPUT:
Counting of input pulses.
Note: The universal counter must also be
parameterized for pulse counting. In the
"ADVANCED > UNIVERSAL COUNTER"
device setting, set the field "SOURCE" to
the value "DIG. INPUT".
ON/OFF-PEAK:
Switching between tariffs. Off-peak if input
active.
DEMAND SYNC:
Synchronization of power demand.
Default:
NONE
PULSES PER
UNIT
The field is available with the action "PULSE INPUT".
Range: 1 to 999
Default: 1
Figure 9-12 "DIGITAL INPUT" device setting
UNIT
Visible with action "PULSE INPUT"
Countable unit with pulse counting:
kWh (active energy)
kvarh (reactive energy)
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...