Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
136
Manual, 02/2008, A5E01168664B-04
INVERT CT POLARITY Inversion of the direction of current flow
ON/OFF switch: ON / OFF.
OFF: SENTRON PAC3200 interprets the direction
of current flow in accordance with the wiring.
On: Direction of current flow is inverted.
SENTRON PAC3200 interprets the direction of current
flow opposite to the wiring.
Default: OFF
9.2.5
Power demand
Device settings for acquiring the power demand.
Call: "SETTINGS > POWER DEMAND."
Figure 9-7
"POWER DEMAND" device setting
Power demand
TIME INTERVAL
Time interval in minutes
Range: 1 to 60 min.
Default: 15 min.
SYNC. VIA BUS
Synchronization via bus
Radio button: ON / OFF.
Default: OFF.
SYNC. VIA DIG.INPUT
Synchronization via digital input
Radio button: ON / OFF.
Default: OFF.
If this option is activated, the "ACTION" field in the "DIGITAL
INPUT" device setting is set to "DEMAND SYNC". See the
chapter "Integrated I/O - DIGITAL INPUT".
See also
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...