Startup
7.6 Applying the measuring voltage
SENTRON PAC3200
100
Manual, 02/2008, A5E01168664B-04
1.
CT PRIMARY: 5000A
2.
CT SECONDARY: 5A
Figure 7-10 Device setting "CURRENT INPUTS - CT PRIMARY?"
7.6
Applying the measuring voltage
The SENTRON PAC3200 with multi-range power supplyis designed for measuring in
systems with rated AC voltages to
●
400 V phase-to-neutral (max. 347 V for UL) and
●
690 V phase-to-phase (max. 600 V for UL).
The SENTRON PAC3200 with extra-low voltage power supplyis designed for measuring in
systems with rated AC voltages to
●
289 V phase-to-neutral and
●
500 V phase-to-phase.
CAUTION
Observe limit values
The limits given in the technical data or on the type plate must not be exceeded even at
startup or when testing the device.
Measurement of DC voltage is not possible.
External voltage transformers are required to measure higher voltages than the permissible
rated input voltages.
See also
Applying the supply voltage (Page 92)
Measuring inputs (Page 22)
Safety notes (Page 73)
Safety notes (Page 17)
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...