Connection
6.2 Connections
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
43
No.
Terminal
Function
(20)
Com
Common = Ground
(21)
+/B
B signal; D1
(22)
-/A
A signal; D0
Figure 6-3
Terminal labeling
Grounding
Conductive panels and doors on control cabinets must be grounded. The doors of the control
cabinet must be connected to the control cabinet using a grounding cable.
Functional ground
DIC
DI0
DI1
DOC
DO0
DO1
(13)
Functional ground terminal
Figure 6-4
Terminal block with 2 digital inputs and outputs, functional ground
The connection "functional ground" discharges interference affecting the digital inputs
and outputs and the RS 485 interface.
Connect the functional ground to the equipotential bonding strip in the control cabinet.
The maximum cable length for connecting the functional ground is 3 meters.
Содержание SENTRON PAC3100
Страница 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Страница 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Страница 100: ...Parameterizing 9 2 Parameterizing the operator interface SENTRON PAC3100 100 Manual 07 2009 A5E02385159B 01 ...
Страница 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Страница 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Страница 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Страница 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Страница 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Страница 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...