Commissioning
6.3 Parameterizing the device
PAC2200CLP
60
Equipment Manual, 06/2021, L1V30820585B-02
6.3
Parameterizing the device
6.3.1
Parameterizing with powerconfig
You can download the powerconfig configuration software from the Industry Online Support
Website (
(https://support.industry.siemens.com/cs/ww/en/view/63452759) herunterladen.
Information and notes on how to use powerconfig can be found in the Online Help of the
configuration software or by contacting Technical Support.
You launch the Online Help in powerconfig by pressing the "F1" key.
Before you can configure the PAC2200CLP power monitoring device, the measuring voltages
must be connected and communication with the device must be set up.
Establishing a connection to PAC2200CLP
Proceed as follows to establish a connection to the PAC2200CLP device:
1.
Connect the PAC2200CLP device to the PC or network.
2.
If you have connected the device via the Ethernet, make sure that the device and the
configuration computer are in the same subnet.
3.
Open the powerconfig configuration software.
4.
On the toolbar, click on the "Search for accessible devices" key or alternatively press the
"F11" key. The "Search for accessible devices" window is displayed.
5.
Click the "Ethernet" tab in the "Search for accessible devices" window:
The "Ethernet" view appears.
–
Select the Ethernet interface from the selection list.
–
Click on the "Start search" button.
–
Select the desired device.
–
If necessary, adapt the communication settings.
–
To do this, switch the edit mode to "Unlocked". Carry out the required settings in the
menu options "IP address", "Network mask", "Gateway" etc. Click on the button "Load
changes to configuration parameters into device(s)".
6.
All devices found are shown in the "Result" window.
7.
Select the desired device and click on the "Create devices" button.
The selected device is added.
Содержание SENTRON PAC2200CLP
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 50: ...Connection 4 4 Connecting the communication cable PAC2200CLP 48 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 60: ...Operation 5 4 Protection against manipulation PAC2200CLP 58 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 86: ...Technical specifications 8 1 Technical specifications PAC2200CLP 84 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 94: ...Dimension drawings 9 1 Dimensional drawings PAC2200CLP 92 Equipment Manual 06 2021 L1V30820585B 02 ...
Страница 129: ......
Страница 130: ......