Functions
5.1 Basic functions
3KC ATC6500 transfer control device
72
Manual, 05/2019, L1V30538268002A-01
5.1.9.2
Table of commands
The following table lists the available commands:
Code Command
Designation on the
ATC
Required
password
Description
C01 Reset maintenance hours
Source 1
RES. MAIN. 1 HRS Advanced Reset maintenance interval hours 1
C02 Reset maintenance hours
Source 2
RES. MAIN. 2 HRS Advanced Reset maintenance interval hours 2
C03 Reset maintenance operations
Breaker 1 (BRK 1)
RES. MAIN. CNT 1
Advanced Reset maintenance interval operations 1
C04 Reset maintenance operations
breaker 2 (BRK 2)
RES. MAIN. CNT 2
Advanced Reset maintenance interval operations 2
C05 Reset counter CNTx
RESET CNT
User
Sets counter CNTx to zero
C06 Reset limits LIMx
RESET LIM
User
Resets the status of the retained LIMx limits
C07 Reset hours counter Source 1 RES. SRC1 HOURS Advanced Resets the hours counter for pres-
ence/absence of Source 1 (see Figure Statis-
C08 Reset hours counter Source 2 RES. SRC2 HOURS Advanced Resets the hours counter for pres-
ence/absence of Source 2 (see Figure Statis-
C09 Reset hours counter Breaker 1
(BRK1)
RES. BRK1 HOURS Advanced Resets the hours counter for the closing /
opening processes of Breaker 1 (see Figure
Statistics (Page 41))
C10 Reset hours counter Breaker 2
(BRK2)
RES. BRK2 HOURS Advanced Resets the hours counters for the closing /
opening processes of Breaker 2 (see Figure
Statistics (Page 41))
C11 Reset operations breaker 1
(BRK1)
RES. BRK1 OPER. Advanced Resets the counting of operating cycles for
Breaker 1 (see Figure Statistics (Page 41))
C12 Reset operations Breaker 2
(BRK2)
RES. BRK2 OPER. Advanced Resets the counting of operating cycles for
Breaker 2 (see Figure Statistics (Page 41))
C13 Reset event log
RESET EVENT LOG Advanced Deletes the list of historical events
C14 Restore default parameters
SETUP DEFAULT
Advanced Resets all the parameters in the Setup menu
to the default values
C15 Saves parameters in backup
memory
BACKUP SETUP
Advanced Stores a copy of the currently set parameters
in a backup memory, so that they can be re-
stored at a later date
C16 Reloading of parameters from
backup memory
RESTORE SETUP Advanced Transfers the parameters stored in the backup
memory to the memory of the active settings
C17 Forced I/O
FORCE I/O
Advanced Enables mode in which you can manually
energize any output.
Note: In this mode, the installation technician
has sole responsibility for the control of the
outputs
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......