Functions
5.1 Basic functions
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
55
5.1.9.2
Table of commands
The following table lists the available commands:
Code Command
Access level required Description
C01
Reset maintenance 1
Advanced
Reset maintenance interval hours 1
C02
Reset maintenance 2
Advanced
Reset maintenance interval hours 2
C03
Reset maintenance operations 1
Advanced
Reset maintenance interval for operating cycles 1
C04
Reset maintenance operations 2
Advanced
Reset maintenance interval for operating cycles 2
C05
Reset general counters CNTx
User
Sets the generic counter CNTx to zero
C06
Reset LIMx limits
User
Resets the status of the retained LIMx limits
C07
Reset hours counter Line 1 / Line 2 Advanced
Resets the hours counter for the presence / ab-
sence of Line 1 and Line 2 within the respective
limits
C08
Reset hour counters Breaker 1 /
Breaker 2
Advanced
Resets the hour counters for the closing / opening
processes of breakers 1 and 2
C09
Reset breaker operation
Advanced
Resets the counting of operating cycles for break-
ers 1 and 2
C10
Reset event log
Advanced
Deletes the list of historical events
C11
Reset default parameters
Advanced
Resets all the parameters in the setup menu to
the default values
C12
Save parameters in backup memory Advanced
Stores a copy of the currently set parameters in a
backup memory, so that they can be restored at a
later date
C13
Reload parameters from backup
memory
Advanced
Transfers the parameters stored in the backup
memory to the memory of the active settings
C14
Forced I/O
Advanced
Enables test mode so you can manually energize
any output.
Note: In this mode, the installation technician has
sole responsibility for the control of the outputs
C15
Reset A03 - A04 alarms
Advanced
Restores the opening or closing command of the
switching devices after generating the alarms A03
- A04
C16
Simulates line failure
Advanced
The device switches to the AUT mode and for two
minutes simulates the failure of the priority line.
After this, it performs a load switchover as pro-
grammed.