Functions
5.1 Basic functions
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
47
5.1.6.1
Properties of the alarms
Various properties can be assigned to each alarm, including the user alarms (UAx see
chapter User alarms (Page 50)).
●
Alarms enabled (active)
General enabling of the alarm.
If an alarm has not been enabled, the procedure is as if the alarm did not exist.
●
Only AUT (Aut)
The alarm can only be triggered if the ATC6300 is in automatic mode.
●
Retention alarm (Retent)
Remains stored, even after the triggering cause has been removed.
●
Global alarm (Glb Al)
Activates the output which is assigned to this global alarm function (see chapter Table of
functions of the digital outputs (Page 112))
●
Lock BRK1 (Lock 1)
On occurrence of the alarm, no further commands are sent to switching device 1.
●
Lock BRK2 (Lock 2)
On occurrence of the alarm, no further commands are sent to switching device 2.
●
Siren (Siren)
Activates the output assigned to this function, as configured in the Table of alarms
(Page 49)
●
Inhibit (Inhib.)
The alarm can be temporarily deactivated by activating a programmable input with the
alarm inhibit function.
●
No LCD (No LCD)
The alarm is managed normally, but not shown on the display.