Technical data
7KT PAC1200 multichannel current measuring system
58
System Manual, 11/2016, 2514374103-02
Measuring accuracy
Data Manager
Voltage
± 0.5 %
Current
± 0.5 %
Active power
± 1.0 %
Apparent power
± 1.0 %
Reactive power
± 1.0 %
Power factor (p.f.)
± 1.0 %
Active energy
Class 1
Reactive energy
Class 1
When using external current transformers, the respective measuring accuracy must be taken
into account.
EMC
ESD (IEC 61000-4-2)
●
4 kV contact discharge
●
8 kV air discharge
RF irradiation
●
3 V / m
Burst (IEC 61000-4-4)
●
Network: ± 4 kV
●
Ethernet: ± 2 kV
Surge (IEC 61000-4-5)
●
Phase-phase: 1 kV
●
Phase-ground: 2 kV
●
Ethernet: ± 2 kV
Conducted interference (IEC 61000-4-6)
●
150 kHz ... 80 MHz
●
RMS value: 3 V
RF irradiation (EN 55022)
●
Class B