Description
2.3 Technical details
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
41
Knowledge Manager
A QR code is attached in a clearly visible location to every 3VA UL molded case circuit
breaker. This code can be scanned with a smartphone or a tablet PC. For the full range of
QR code functions, use the "Industry Support" app supplied free of charge by Siemens.
All relevant product information regarding the molded case circuit breaker (e.g. operating
instructions, characteristic curves, FAQs, etc.) can be quickly accessed and viewed in this
way.
Key electrical data NEMA
The key electrical data for the UL market on the left side of the molded case circuit breaker
(when viewed from above) contains the following information:
①
UL, CSA and NOM approval marks, if valid for this circuit breaker
②
NEMA breaking capacity values with various voltages
③
HID type information (see below)
④
HACR type information (see below)
HID and SWD type information
15 and 20 A circuit breakers marked "SWD" are suitable for use in applications, up to 347 V,
intended to switch fluorescent lighting loads on a regular basis.
SWD stands for Switching Duty.
15-50 A circuit breakers marked "HID" are suitable for use in applications intended to switch
fluorescent High-Intensity-Discharge lighting loads on a regular basis.