7.8.3
HSR Coupling Configuration
HSR Coupling Configuration
The HSR-specific parameters are entered in the "Coupling Configuration" dialog box.
Figure 7-18 X204 Coupling Configuration
"Coupling Mode"
Here you can set the coupling mode between HSR and the remaining network.
Coupling Mode
Meaning
HSR SAN Mode
The HSR ring is connected with Standard Ethernet end devi‐
ces or network segments (default).
Non Redundant HSR PRP coupling
Setting with non-redundant HSR<->PRP coupling. P1/A is
connected with LAN A, P2/B with LAN B of a PRP network.
Redundant HSR PRP coupling, LAN A
Setting with redundant HSR<->PRP coupling. P1/A is con‐
nected with LAN A of a PRP network. P2/B is open and may
not be used.
Redundant HSR PRP coupling, LAN B
Setting with redundant HSR<->PRP coupling. P1/B is con‐
nected with LAN B of a PRP network. P1/A is open and may
not be used.
Functional description and configuration using Web Based Management
7.8 The "X200" menu
SCALANCE X-200RNA
98
Operating Instructions, 10/2016, C79000-G8976-C342-04
Содержание SCALANCE X-200RNA
Страница 6: ...Table of contents SCALANCE X 200RNA 6 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 12: ...Introduction SCALANCE X 200RNA 12 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 16: ...Safety notices SCALANCE X 200RNA 16 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 54: ...Descriptions of the products 4 8 LEDs SCALANCE X 200RNA 54 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 62: ...Installation 5 3 Wall mounting SCALANCE X 200RNA 62 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 70: ...Connecting up 6 4 Grounding SCALANCE X 200RNA 70 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 142: ...Approvals and marking SCALANCE X 200RNA 142 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 146: ...Technical specifications SCALANCE X 200RNA 146 Operating Instructions 10 2016 C79000 G8976 C342 04 ...