Connection
5.1 Lightning protection, power supply and grounding
SCALANCE W774-1 /W734-1
36
Operating Instructions, 01/2017, C79000-G8976-C325-08
5.1
Lightning protection, power supply and grounding
Lightning protection
WARNING
Danger due to lightning strikes
Antennas installed outdoors must be within the area covered by a lightning protection
system. Make sure that all conducting systems entering from outdoors can be protected by
a lightning protection potential equalization system.
When implementing your lightning protection concept, make sure you adhere to the VDE
0182 or IEC 62305 standard.
Suitable lightning protectors are available in the accessories (Page 15) of SIMATIC NET
Industrial WLAN.
Note
We recommend that you use the maintenance-free lightning protector LP798-2N.
Exception: When there is also DC power supplied via the antenna cable. In this case, only
the lightning protector LP798-1N can be used.
WARNING
Danger due to lightning strikes
Installing this lightning protector between an antenna and a SCALANCE W700 is not
adequate protection against a lightning strike. The LP798-1N lightening protector only
works within the framework of a comprehensive lightning protection concept. If you have
questions, ask a qualified specialist company.
Note
The requirements of EN61000-4-5, surge immunity tests on power supply lines, are met only
when a Blitzductor is used with 24 VDC:
BVT AVD 24
type no. 918 422
Manufacturer: DEHN+SÖHNE GmbH+Co.KG, Hans Dehn Str. 1, Postfach 1640, D -
92306 Neumarkt, Germany
Содержание SCALANCE W734-1
Страница 50: ...Connection 5 6 Grounding SCALANCE W774 1 W734 1 50 Operating Instructions 01 2017 C79000 G8976 C325 08 ...
Страница 62: ...Approvals SCALANCE W774 1 W734 1 62 Operating Instructions 01 2017 C79000 G8976 C325 08 ...
Страница 64: ...Index SCALANCE W774 1 W734 1 64 Operating Instructions 01 2017 C79000 G8976 C325 08 ...