99/106
Siemens
Basic Documentation RVP360
CE1P2546en
Building Technologies
22 Engineering
2017-07-24
22 Engineering
22.1 Connection terminals
Low-voltage side
Mains voltage side
DB Data LPB
N
Neutral conductor AC 230 V
MB Ground for LPB
L
Live AC 230 V
A6 PPS (point-to-point interface), connection of room
unit heating circuit 1 and heating circuit 2
F4 Input for K4
MD Ground for PPS
K4 1. 1st burner stage
B9 Outside sensor
F5 Input for K5
B1 Flow sensor heating circuit 1
K5 2. burner stage
B12 Flow sensor heating circuit 2
F3
Input for Q1 and Q3
M Ground for sensors
Q1 Circulating
pump
B31 Storage tank sensor/thermostat at the top
Q3 Storage tank charging pump
B32 Storage tank sensor/thermostat at the bottom
F1/F2 Input for Y1 and Y2
B7 Return sensor
Y1
Heating circuit mixing valve heating circuit 1
OPEN
B5 Room sensor heating circuit 1
Y2
Heating circuit mixing valve heating circuit 1
CLOSE
B52 Room sensor heating circuit 2
F7
Input for Q2, Q6 and K6
B6 Collector sensor
Q2
Heating circuit pump heating circuit 1
Q6
Heating circuit pump heating circuit 2
In addition to the standard connection terminals,
auxiliary terminals for M are provided
K6 Multifunctional
relay
F6
Input for Y7 and Y8
Y7
Heating circuit mixing valve heating circuit 2
OPEN
Y8
Heating circuit mixing valve heating circuit 2
CLOSE
In addition to the standard connection terminals, auxiliary
terminals for N and
are provided