19 Function block: Locking functions
2017-07-24
19 Function block: Locking functions
All settings can be locked on the software side to prevent tampering.
19.1 Operating line
Line Function, parameter
Factory setting
(range)
Unit
Heating
circuit
248
Locking of settings
0 (0 / 1)
–
–
19.2 Locking settings on the software side
Operating line 248 can be used to lock on the software side the settings made on
the controller. This means that all settings made can still be queried on the control-
ler, but cannot be changed anymore.
The settings can be changed via bus.
The procedure is as follows:
1. Press
and
simultaneously until
appears on the display.
2. Press
,
,
and
, one after the other.
3. Now, operating line 248 appears on the display. The following locking choices
are available:
0 = no locking
1 = all settings are locked
After locking all settings, the following operating elements remain active:
The buttons for selecting the operating lines
No longer active are …
the buttons for making readjustments of values,
the knobs for readjustment of the room temperatures,
the operating mode buttons (only for leaving the setting level),
the button for manual control.