14 Function block: D.h.w.
2017-07-24
Op. line
121
Op. line
123
Con-
troller
Oper.
mode
Heating program,
optim., holidays
Release
2
1
A (HC1)
06:00...18:00, no op-
timization
D.h.w. heating is
released from
04:00 to 23:00
A (HC2)
07:00...23:00
B (HC1)
07:00...22:00, opti-
mized switching on
produces a forward
shift of 2 hours
B(HC2)
03:00...22:00, holi-
days
Op. line
121
Op. line
123
Con-
troller
Oper.
mode
Heating program,
optim., holidays
Release
2
1
A (HC1)
06:00...18:00, no op-
timization
D.h.w. heating is
released from
04:00 to 23:00
A (HC2)
08:00...23:00
B (HC1)
07:00...22:00, opti-
mized switching on
produces a forward
shift of 2 hours
B(HC2)
05:00...21:00
14.5.3 D.h.w. heating during holiday periods
In holiday mode, d.h.w. heating is provided as follows:
Op. line
121
Op. line
123
D.h.w. heating
0
0, 1 or 2 No d.h.w. heating when own controller operates in holiday
mode
1
0, 1 or 2 No d.h.w. heating when all controllers in the same segment
operate in holiday mode
2
0, 1 or 2 No d.h.w. heating when all controllers in the interconnected
system operate in holiday mode
14.6 Priority and flow temperature setpoint
14.6.1 Settings
Op. line
124
D.h.w. priority
Flow temperature
setpoint according to …
0
Absolute
d.h.w.
1
Shifting
d.h.w.
2
Shifting
maximum selection
3
None (parallel)
d.h.w.
4
None (parallel)
maximum selection
Example 1
Example 2