12 Function block: Boiler
2017-07-24
12.3 Limitations
12.3.1 Maximum limitation of boiler temperature
For maximum limitation of the boiler temperature, the maximum limit value can be
set. The switch-off point cannot be higher than the maximum limit value.
The switch-on point is then lower, the difference being the set switching differential.
If the boiler temperature is limited to a maximum, the display shows
.
This maximum limitation is not a safety function; for that purpose, a thermostat,
thermal reset limit thermostat, etc., must be used!
12.3.2 Minimum limitation of boiler temperature
For minimum limitation of the boiler temperature, the minimum limit value can be
set. The switch-on point cannot fall below the minimum limit value.
The switch-off point is then higher, the difference being the set switching differen-
tial.
If the boiler temperature is limited to a minimum, the display shows
.
12.3.3 Actions during d.h.w. heating
Maximum and minimum limitation are also active during d.h.w. heating.