5 Function block: End-user space heating
2017-07-24
5.3 Heating
program
The heating program offers a maximum of 3 heating phases per day; in addition,
every weekday can have different heating phases.
The inputs to be made are not the switching times, but the periods of time during
which the NORMAL room temperature shall be maintained. These periods of time
are usually identical with the building's occupancy times. The effective switching
times for changing from the REDUCED to the NORMAL room temperature, and
vice versa, are calculated by the optimization function ( precondition: optimization
is activated).
Using setting "1-7" on operating line 4, a heating program applying to all weekdays
can be entered. This simplifies the settings. If weekend times differ, enter the times
for the entire week first, then change days 6 and 7 as required.
The entries are sorted and overlapping heating phases are combined.
5.4 Holiday
program
One holiday period per year can be programmed. At 00:00 of the first day of the
holiday period, switching over to the setpoint for holiday/protection mode takes
place. At 24:00 of the last day of the holiday period, the controller switches to
NORMAL or REDUCED heating in accordance with the time switch settings.
The settings for the holiday period are cleared as soon as the holidays have
elapsed.
The holiday function switches off d.h.w. heating and the circulating pump, depend-
ing on the settings made on operating line 121.
The holiday program is only active in AUTO mode.
5.5 Heating
curve
The heating curve can be adjusted on operating lines 14 and 15. For more
detailed information, refer to chapter 9.6 "Heating curve".